functionID | name |
---|---|
000a | Room temperature controller master with fan |
000b | Room temperature controller slave |
0023 | Room temperature controller master without fan |
pairingID | in/out | name | value |
---|---|---|---|
51 | out | Defines the displayed set point temperature of the system | temperature in °C |
54 | out | states: on/off; heating/cooling; eco/comfort; frost/not frost |
bitmask:
0x01 - comfort mode
0x02 - standby
0x04 - eco mode
0x08 - building protect
0x10 - dew alarm
0x20 - heat (set) / cool (unset)
0x40 - no heating/cooling (set)
0x80 - frost alarm
|
56 | out | Switches controller on or off. Off means protection mode | 1
0 - off (Protection mode)
1 - on (Comfort mode or Eco mode)
|
58 | in | Switches eco mode on or off |
0 - off
1 - on
|
66 | in | Request for switching controller on or off. Off means protection mode |
0 - off (Protection mode)
1 - on (Comfort mode or Eco mode)
|
304 | out | Indicates the actual measured temperature | temperature in °C |
320 | in | Absolute set point temperature input for timer | temperature in °C |